CESRA PIR DSI
Images shown are for illustration purposes only and may not be an exact representation of the productCESRA PIR DSI
Ceiling Surface Mounted
CESRA PIR DSI can be used to control up to 20 high frequency DSI dimmable ballasts. They incorporate a passive infra-red quad sensor to detect movement of a warm body within its detection zone and a photocell to monitor the ambient light level. These products are hard wired and can be mounted directly onto solid ceilings or onto a range of different mounting boxes. CESRA PIR DSI operates by Absence Detection. It requires a retractive (momentary) switch to be pressed when a person enters the room. This will switch the lights ON and enable the PIR switch to control the load. The load will automatically be switched OFF or to its reduced lux level (minimum) when no further movement is detected for its RUN-ON time.
Detection Zone
360°
Time lag range
10 seconds to 40 minutes in 9 steps
Run-on time
0, 1, 2, 5, 10, 15, 20, 30 mins and infinite (always ON at minimum)
Photocell range
30 to 1000 lux, and inactive
Loading
Daylight linked dimming with occupancy switching. For controlling DSI dimmable ballasts. The external DSI power supply provided can control up to 40mA, eg. 20 ballasts at 2mA (varies according to make and model of ballasts). For greater numbers of ballasts (64 max.)additional external DSI Power supplies can be purchased (DANLERS order code: DBPSU). These controls can also switch up to 6 amps (1500W) of dimmable fluorescent lamps. 2 amps (500W) of CFL, LED Drivers and LED lamps and fittings.
Dimensions
91mm diameter x 45mm